Zhengzhou Great Electric Co.,Ltd.

Grow with our partner n the wordwide

Manufacturer from China
Active Member
5 Years
Home / Products / CT PT Test Equipment /

Cabinet Type CT PT Test Equipment System Error Measurement

Contact Now
Zhengzhou Great Electric Co.,Ltd.
City:zhengzhou
Province/State:henan
Country/Region:china
Contact Person:MrTony Han
Contact Now

Cabinet Type CT PT Test Equipment System Error Measurement

Ask Latest Price
Video Channel
Brand Name :HNMC
Model Number :MCHZDT-3Z
Place of Origin :China
MOQ :1
Price :Negotiable
Payment Terms :L/C, T/T, Western Union
Supply Ability :10 sets per month
Delivery Time :30-45 days
Packaging Details :Wooden Package
Standard CT Class :0.05, 0.02....0.005 (optional)
Digital Transformer Tester :2%
Application :Lab, CT PT Manufacturer
Rated Capacity :25KVA
Current range :5-5000A
Rated Secondary :1A, 5A
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Cabinet Type CT PT Test Bench System MCHZDZ-3Z

System Configuration

1) HZDT Fully automatic Cabinet type Control Bench

2) Digital Transformer Tester

3) Current Transformer Burden (5A/1A optional)

4) Standard Current Transformer ( with Current Source)

5) Voltage Transformer Burden

6) Standard Voltage Transformer ( with Voltage Source)

7) Current Transformer Primary Testing Cable

8) CT & PT Secondary Testing Cable

9) PC Test software

Main Function

Ratio error and phase angle error test of CT & PT

Technical Parameter & Features

HES-10 CT&PT Test Bench

Input Voltage AC 220+/-10% 50HZ+/-0.5hz
Output voltage AC 0-250V
Rated Capacity 25KVA
“Open-circuit demagnetization”, “Closed-circuit demagnetization”, “Error measurement”
Over current protection:>100A
FY current transformer burden,FY voltage transformer burden,HES-1C Digital Transformer Tester,Other Control function etc

Digital Transformer Tester

Voltage Range 150V, 100V, 100/√3V (customization available)
Current range 5A, 5A(S), 1A, 0.5A
Accuracy class 2.0
Ratio error ±0.0001% ~ ±19.99%
Phase error ±0.01' ~ ±900'
Impedance 0.001Ω~ 19.99Ω. Minimum resolution: 0.001Ω
Admittance 0.001 ms ~ 19.99ms. Minimum resolution:0.001 ms
Rated frequency 50 or 60HZ

Standard Current Transformer with current generator

Rated primary current(A) 5-5000A
Rated secondary current 5A or 1A
Accuracy class 0.02%, 0.05%, 0.05S%, 0.01%, 0.005% (optional)
Rated secondary load 0.2 ohm
Frequency 50HZ
Operating Range 1%--120%
Capacity of Current Source 25kVA or more

Fully automatic Current transformer burden box

Rated Current 5A, 1A
Operating Range 1%--120%
Rated load (VA) 2.5VA-60VA (customization is available)
Rate Frequency 50Hz or 60HZ
Accuracy Class ±3%
Power factor 0.8, 1.0
Full automatic, three phases can be tested at the same

Fully automatic Voltage transformer burden box

Rated voltage 100V, 100/√3V or more options
Operation Range 20%--120%
Rated load 1.25VA-80VA (customization is available)
Fundamental error ±3%
Power factor 0.8, 1.0
Rated Frequency 50Hz or 60Hz

Standard Voltage Transformer with Voltage Generator

Rated primary voltage 6kV,10kV,15kV,22kV,35kV or more option
Rated secondary voltage 100V,100/√3V,110V,110/√3V, or more option
Accuracy class 0.05% or higher accuracy class
Secondary capacity 0.5VA or more option
Power factor cosΦ=1.0
Power frequency 50HZ
Range of operating voltage 20%--120%

Cabinet Type CT PT Test Equipment System Error Measurement

Cabinet Type CT PT Test Equipment System Error Measurement

Inquiry Cart 0