Protection Relay Test Kit MCRT43N
Features
- High power & reliable amplifier
- Adopting DSP technology
- Stable and Reliable Output
- Good accuracy
- Self-protection function
- Modularization Design & Mutual independent between different parts
- Graphical testing modules and templates for testing of various relays
- Electric meter testing (optional)
- Transducer Testing (optional)
- GPRS sync end-to-end testing (optional)
- Transient Playback
- Automatically create test report
- Wrong wiring alarm and, overload and overheat protection
- Operated by in-built computer or by PC
AC volts source | MAX output voltage | 4×150V |
MAX output power | 4×75VA |
resolution | 5mV |
Accuracy | ≤0.2% |
Harmonic distortion | ≤0.2% |
Other | Output amplitude/frequency/phase of each phase can be adjustable independently, and with short circuit protection and over current protection |
AC current source | MAX output current | 3×35A or 1×105A |
MAX output power | 3×300VA or 1×900VA |
resolution | 1mA |
Accuracy | ≤0.2% |
Harmonic distortion | ≤0.2% |
Other | Output amplitude/frequency/phase of each phase can be adjustable independently, and with open circuit protection and over load protection |
DC Volts | MAX output voltage | 4×150V |
MAX output power | 4×75W |
Accuracy | ≤0.2% |
Other | Short-circui,over-current protection |
DC current | MAX output current | 3×35A or 1×105A |
MAX output power | 3×300W or 1×900W |
Accuracy | ≤0.2% |
Other | Open circuit,Over-load protection |
AUX DC voltage | Output | 0~250V continuously adjustable; Fast switch between 24,110V,220V; Output Power:120W |
other | Short circuit,over-load protection |
Phase | range | -360°~ +360° |
accuracy | 0.01° |
frequency | range | DC 10~1000Hz |
resolution | 0.001Hz |
drifting | 5ppm |
Binary input | Quantities | 8 pairs |
Response time | 50μs |
timing range | 1ms~999,999.999s |
Input way | Idle contact or Potential automatic identification,withstand voltage 250V |
Other | Auti-shake time adjustable |
Binary output | Quantities | 4 pairs |
Output way | Idle contact, withstand voltage 250V ,capacity 250VA |
DC measurement (transducer calibration) | Voltage | one group, input±10V, accuracy <0.05% |
Current | one group, input ±20mA,accuracy <0.05% |
impulse | Max receivable frequency 30KHz |
Energy Meter Calibration | Type of meter under test | Electromechanical & Electronic |
Pulse Range | Maximum frequency 2MHZ |
Test Function | Error test |
Configuration | 1 No optical sensor |
Key board | In-built | 24 keys |
external | RS232 |
Display screen | size | 8.4 `` |
resolution | 800×600 |
color | TFT |
Touching screen LCD | 8.4`` |
Mouse | PS/2 port |
USB port | One |
Web port | one |
size | 471mm×192mm×363mm |
weight | 16.3kgs |
Power Supply | Single phase AC 90-260V, 50/60HZ, 3KW/15A |